FOCUS INDUSTRY

Saving energy with refrigeration dryers

If you want to reduce the energy costs of your compressed air supply, you should take a look at your dryers as well as your compressors. Cost savings are possible with variable-speed refrigerating compressors, control of the pressure dew point as well as by minimizing the pressure loss during condensate precipitation. The energy consumption of the compressed air supply can be influenced mainly with modern compressor systems such as speed control (VSD, Variable Speed Drive). Even for supposedly smaller energy consumers, like e.g. refrigeration dryers, energy consumption can be lowered by up to 35 % without any great effort – and that with only low additional investment.

Conventional compressed air refrigeration dryers are usually designed to operate continuously. They always operate with 100-% output – even if this is not always needed – and consume a constant level of energy. Refrigeration dryers with speed-controlled refrigerant compressors (Fig.) on the other hand adjust the energy consumption precisely to match the demand defined based on the moisture load. Alternatively the energy consumption can be reduced with the Saver Cycle control system from Atlas Copco. Here the refrigerant compressor is shut down when volume flows are low or the ambient temperature is high. This enables a significant energy saving. The lower the volume flow, the higher the saving can be. The relative air humidity of the compressed air at the exit from the dryer is kept below 50 % at every point in time. This ensures that all compressed air consumers are protected against corrosion.

Going beyond the control options, the pressure loss of the refrigerating dryer describes the efficiency of the equipment. For the compressed air and condensate must be separated, if possible without any pressure loss. After all, the nominal pressure must be reached. The higher the pressure loss, the more the compressor must compress. In a comparison of two refrigerating dryers, each downstream of a
200-kW screw-type compressor, one working with a pressure loss of 0.35 bar, the other with 0.2 pressure loss, the following could be established: the lower pressure loss of the second dryer alone cuts the energy bill by around € 9000 within five years, assuming 8600 operating hours per year and electricity costs of 0.1 €/kWh.

Atlas Copco Kompressoren und Drucklufttechnik GmbH, Essen (D),
Tel.: +49 201 2177-0,
www.atlascopco.com

x

Related articles:

Issue 2009-11

Lead recycling with volume-flow-controlled compressed air station

With a new low-pressure compressed air station incorporating six speed-controlled, turbo-compressors work, the Weser-Metall GmbH lead works in Nordenham saves up to € 600 000 per year in energy...

more
Issue 2019-04 AERZEN

AERZEN

T?he successful screw compressor generation Delta Screw from AERZEN gets an addition: With the VM 100 compressor package, the versatile E-Compressor series now comprises seven model variants. Its...

more
Issue 2022-09 Efficient compressed air

Electric mobile air compressors help in manganese extraction

One of the world’s largest manganese producers Mexico’s Autlán needs compressed air for its production. The solution is Atlas Copco’s E-Air V1100 Variable Speed Drive (VSD) electric compressors....

more
Issue 2019-04 Atlas Copco

Atlas Copco

A?t the Powtech trade fair,?Atlas Copco is presenting new low-pressure compressors, as well as screw and lobe blowers for energy-efficient pneumatic conveyor systems, e.g. for applications in the...

more
Issue 2012-10

Extension of new rotary lobe compressor series

Relying on experience in the design and production of rotary lobe blowers since 1868 and screw compressors since 1943 Aerzen has continually set new standards for quality and innovation in the field...

more